Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23 335
11 Drive Dimensioning
11.4 Lenze gearbox selection
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Alternating load or pulsating load?
According to the intensity of the periodically occurring alternating load, the alternating load
factor k
alt
is in the range of 1 ... 1.4.
In the case of a symmetrical alternating load M
alt,out
=M
max,out
, the alternating load
factor k
alt
is 1.4.
An alternating load without sign reversal (no torque reversal) is a pulsating load. The alternat-
ing load factor for pulsating loads is k
alt
=1.
[11-12] Different torque characteristics at the output end of the gearbox
•Pulsating load
The torque alternates between two values without sign re-
versal
Alternating load factor k
alt
= 1
•Pulsating load
The torque changes from 0 to the max. value without sign
reversal
Alternating load factor k
alt
= 1
•Alternating load
Torque reversal with sign reversal
Alternating load factor k
alt
> 1 (here approx. 1.13)
M
out
t
M
max,out
M
alt,out
t
M
out
M
max,out
t
M
out
M
max,out
M
alt,out