11 Parameter reference
11.2 Parameter list | C01501
418
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01501
C01503
Parameter | Name:
C01501 | Resp. to communication error with MCI
Data type: UNSIGNED_8
Index: 23074
d
= 5A22
h
Configuration of monitoring modes for the communication unit
Selection list
0 No Reaction
1Fault
4 WarningLocked
Subcodes Lenze setting Info
C01501/1 1: Fault Resp. to MCI error 1
• Response to a communication error.
C01501/2 1: Fault Resp. to MCI error 2
• Response to an incompatible communication unit.
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C01503 | MCI timeout
Data type: UNSIGNED_16
Index: 23072
d
= 5A20
h
Setting range (min. value | unit | max. value)
0 ms 1000
Subcodes Lenze setting Info
C01503/1 200 ms MCI timeout
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1