11 Parameter reference
11.2 Parameter list | C00118
352
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00118
C00120
C00122
Parameter | Name:
C00118 | DOx inversion
Data type: UNSIGNED_8
Index: 24457
d
= 5F89
h
The polarity of each digital output of the device can be inverted via this bit field.
Setting range (min. hex value | max. hex value) Lenze setting
0x00 0xFF 0x00 (decimal: 0)
Value is bit-coded: ( =bit set) Info
Bit 0 Relay inverted Relay inversion
Bit 1 DO1 inverted Inversion of digital output 1
Bit 2 Reserved
Bit 3 Reserved
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00120 | Setting of motor overload (I²xt; C0088/C0098)
Data type: INTEGER_16
Index: 24455
d
= 5F87
h
The Inverter Drives 8400 are provided with a simple, sensorless, thermal I²xt motor monitoring of self-ventilated
standard motors which is based on a mathematical model.
• For setting notes, see chapter "Motor overload monitoring (I2xt)
".
• The response for triggering the monitoring can be selected in C00606
.
• The current thermal motor load is displayed in C00066
.
Setting range (min. value | unit | max. value) Lenze setting
0 % 250 100 %
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00122 | Initial value motor overload (I²xt)
Data type: UNSIGNED_16
Index: 24453
d
= 5F85
h
From version 04.01.00
The thermal motor load displayed in C00066
is pre-initialised with the value set here when the device is connected
to the mains.
• If "100.00 %" is set, the last value at switching off the device is used for the initialisation.
• Recommended setting for operation according to UL: 50.00 %
Motor overload monitoring (I2xt)
Setting range (min. value | unit | max. value)
0.00 % 100.00
Subcodes Lenze setting Info
C00122/1 0.00 % Initial value motor overload (I²xt)
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100