7 Technology applications
7.2 TA "Actuating drive speed"
202
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.2.1 Basic signal flow
When you go to the Application parameters tab to the top dialog level Overview and click the Signal
flow button, you will get one dialog level down to the signal flow of the application (here displayed
with the preset control mode "Terminals 0"):
Configuration parameters for digital control signals:
Motor potentiometer (L_MPot_1) Device control (LS_DriveInterface)
Setpoint generator (L_NSet_1
) Motor control (MCTRL)
Process controller (L_PCTRL_1) "GeneralPurpose" functions
All input and output interfaces of the application are described in the chapter entitled
"Interface description
". ( 206)
Parameter
Selection of signal source
(Lenze setting)
for control signal:
bMPotUp
(C00701/8)
0: Not connected L_MPot_1: Increase speed setpoint
bMPotDown
(C00701/9)
0: Not connected L_MPot_1: Decrease speed setpoint
bMPotInAct
(C00701/10)
0: Not connected L_MPot_1: Activate inactive function
bMPotEnable
(C00701/11)
0: Not connected L_MPot_1: Activate motor potentiometer function
Page view 201