Lenze 8400 motec User Manual Page 343

  • Download
  • Add to my manuals
  • Print
  • Page
    / 518
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 342
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05 343
11 Parameter reference
11.2 Parameter list | C00056
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00056
C00057
C00058
C00059
C00061
Parameter | Name:
C00056 | Torque
Data type: INTEGER_32
Index: 24519
d
= 5FC7
h
Display of the current torque
Display range (min. value | unit | max. value)
-320.00 Nm 320.00
Subcodes Info
C00056/1 Torque demand
• Only in case of sensorless vector control (SLVC
).
C00056/2 Actual torque value
• Estimated actual torque for all motor control modes.
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00057 | Maximum torque
Data type: UNSIGNED_32
Index: 24518
d
= 5FC6
h
Display of the maximum torque to be generated by the motor
• The maximum torque to be generated by the motor depends on various factors, e.g. on Imax in motor mode
(C00022
) and the motor type used.
Display range (min. value | unit | max. value)
0.00 Nm 320.00
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00058 | Output frequency
Data type: INTEGER_32
Index: 24517
d
= 5FC5
h
Display of the current output frequency
Display range (min. value | unit | max. value)
-655.0 Hz 655.0
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00059 | Appl.: Reference frequency C11
Data type: UNSIGNED_32
Index: 24516
d
= 5FC4
h
Display of the field frequency which corresponds to the reference speed set in C00011.
Display range (min. value | unit | max. value)
0.0 Hz 999.9
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00061 | Heatsink temperature
Data type: INTEGER_16
Index: 24514
d
= 5FC2
h
Display of the current heatsink temperature
Display range (min. value | unit | max. value)
-50 °C 150
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Page view 342
1 2 ... 338 339 340 341 342 343 344 345 346 347 348 ... 517 518

Comments to this Manuals

No comments