Lenze E82ZAFIC010 User Manual Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 71
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
Installation
Electrical installation
Wiring according to EMC (CE−typical drive system)
5
l
19
EDS82ZAFIC EN 2.0
5.2 Electrical installation
5.2.1 Wiring according to EMC (CE−typical drive system)
For wiring according to EMC requirements observe the following points:
) Note!
ƒ Separate control cables/data lines from motor cables.
ƒ Connect the shields of control cables/data lines at both ends in the case of
digital signals.
ƒ Use an equalizing conductor with a cross−section of at least 16mm
2
(reference:PE) to avoid potential differences between the bus nodes.
ƒ Observe the other notes concerning EMC−compliant wiring given in the
documentation for the standard device.
Wiring procedure
1. Observe the bus topology, do not use any stubs.
2. Follow the wiring notes given in the documentation for the control system.
3. Only use cables which comply with the specifications listed ( 20).
4. Observe the notes concerning the voltage supply of the function module ( 21).
Page view 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 70 71

Comments to this Manuals