6 Electrical installation
Assignment of the terminals
EDK82ZAFCC-010 DE/EN/FR 5.0
48
H2_BelegungAnschlKlemmen-INS_Klembesch
X3.1/ Designation Function Level
7 GND1 Reference potential 1
LO CAN-LOW System bus LOW (data line)
HI CAN-HIGH System bus HIGH (data line)
X3.2/ Designation Function Level
7 GND1 Reference potential 1
39 GND2 Reference potential 2 of the controller
inhibit (CINH) at X3.2/28
28 CINH Controller inhibit (CINH)
Start = HIGH (12 ... 30 V)
Stop = LOW (0 ... 3 V)
20 DC voltage source for internal supply of
controller inhibit (CINH)
20 V (Ref: GND1)