Commissioning
Initial switch-on
7
EDK82ZAFCC-010 DE/EN/FR 5.0
53
H2_FirstOn-INB_01
Initial switch-on
Note!
ƒ
Code C0356/x serves to set the times for
cyclic
transmission.
ƒ
The CAN master can access the Lenze codes saved to the controller via the
index.
Index = 24575 – Lenze code number (Cxxxx)
ƒ
The controller is only ready for operation if a HIGH level is applied to
terminal 28 of the function module (controller enable via terminal).
Please observe that the controller can be inhibited through various
sources. All sources act like a series connection of switches.
If the drive does not start in spite of the controller enable via terminal
28, check whether the controller is still inhibited via another source such
as the key of the keypad.
Step Description
1. Configure master system (CAN master) for communication with the function module.
2. Inhibit standard device via terminal 28 (CINH).
Set terminal 28 to LOW level.
The standard device can be inhibited and enabled via the bus subsequently.
3. Switch on the mains voltage.
The standard device will be ready for operation after approx. 1 second.
The controller inhibit is active.
Response of standard device
The green LED is blinking.
Keypad:

(if plugged-in)
4.
A Set node address via ...
C0350 or
DIP switch (if available).
(Lenze setting: 500 kbps)
A node address in a CAN network must not be used more than once.
B Set baud rate via ...
C0351 or
DIP switch (if available).
(Lenze setting: 1)
All CAN nodes must have an identical baud rate.
Changes will not be accepted until a ”Reset node” command (C0358 = 1) has been
executed.