Page view 17
Technical data
General data and operating conditions
4
18
LDCDS−EL100 EN 9.0
4 Technical data
4.1 General data and operating conditions
Conformity and approval
Conformity
CE
EN 61000−6−1 (−3),
VDE 0839−6−1 (−3)
2002 residential area
EN 61000−6−2 (−4),
VDE 0839−6−2 (−4)
2006 industrial premises
EN 55022
EN 55024 Equipment of information technology
Approbation
UL UL 508
CSA C22.2
Programmable Controllers (File−No. E236341)
Other
RoHS Products lead−free in accordance with CE Directive
2011/65/EU
Protection of persons and equipment
Safety VDE0805 (EN60950),
VDE0870, UL
Type of protection IP65 (front) / IP20 (back)
Type 1, 2 and 5 enclosure
Class of protection 3
Ambient conditions
Climatic
Temperature
Storage/Transport 0 ... +60 °C
Operation
EL 1xx ECO
EL 1xx CAN/MPI
0 ... +50 °C
EL 1xx ECO PLC
EL 1xx PLC
5 ... +45 °C
Relative humidity 10 ... 90 %, no condensation
Site altitude
Storage/Transport < 12.000 m amsl
Operation < 3.000 m amsl
Vibration test according to EN 61131−2 (programmable controllers)
Vibration EN 60068−2−6 1 g
Shock EN 60068−2−27 15 g
Mounting conditions
Mounting place
Control cabinet door
Mounting position Terminals at the bottom