Modbus RTU & Modbus TCP/IP CommunicationCommunications Interface Reference Guide
10P94MOD01C Installation3.2 Connectors3.2.1 EIA-485 ModuleTable 2 and Figure 3 illustrate the pinout of the PositionServo EIA-485 (RS485) Option Modu
11 P94MOD01CInstallation3.3 Electrical Installation3.3.1 Cable TypesDue to the high data rates used on Modbus networks it is paramount that correctl
12P94MOD01C Installation• Maximum cable length for UTP/STP CAT5e cable is typically 100m. For other categories consult the cable data sheet.• Use fib
13 P94MOD01CInstallation3.3.5 Connections and Shielding: EthernetThe use of pre-fabricated cables is recommended as this reduces the chances of conne
14P94MOD01C Installation3.3.8 Network Schematic: EIA-485Figure 7 illustrates the connection of the cables for a PositionServo drive in a Modbus maste
15 P94MOD01CCommissioning4 Commissioning4.1 OverviewIt is assumed that the user has familiarised themselves with how to set parameters using MotionVie
16P94MOD01C CommissioningFigure 10: Example Modbus Register Assignment6. Repeat steps 3 to 5 for each required slave/server nodeFigure 11: Example Mo
17 P94MOD01CCommissioning4.3 Configuring the PositionServo Slave/Server4.3.1 ConnectingWith the drive power disconnected, install the EIA-485 (RS485)
18P94MOD01C Commissioning4.3.3 Modbus RTU Slave Node SettingsIf using the EIA-485 (RS485) module, open MotionView and click on the [Communication] fo
19 P94MOD01CCommissioningFigure 15: Modbus RTU Folder4.3.4 Modbus TCP/IP Server Node SettingsThe IP address of the PositionServo drive is composed of
2P94MOD01C Copyright ©2005 by Lenze AC Tech Corporation.All rights reserved. No part of this manual may be reproduced or transmitted in any form witho
20P94MOD01C Commissioning4.3.4.2 Configuring the IP Address Manually (Static Address)When connecting directly from PositionServo drive to the PC witho
21 P94MOD01CCommissioningTo disable DHCP, click the box again. Power must be cycled for any changes to [Configure IP Address] to take effect. On changi
22P94MOD01C Commissioning4.4 Drive MonitoringThe master/client can read the drive parameters as long as Modbus communications are enabled.NOTE:The co
23 P94MOD01CCommissioning4.8 Ethernet ParametersDrive variables #67-70 are Ethernet communication programming parameters specifically for configuration
24P94MOD01C Protocol Implementation5 Modbus Implementation5.1 Supported Function CodesThe Modbus function codes supported by the PositionServo drive
25 P94MOD01CProtocol ImplementationTo access the <variable index> as EPM-float, use the following formula to calculate this register address (max
26P94MOD01C Protocol Implementation5.4 Endian FormatModbus uses “big-endian” representation of the register data. This means that when a numerical va
27 P94MOD01CProtocol Implementation5.7 Exception ResponsesIf an invalid message is received, the drive will respond with a Modbus Exception as per th
28P94MOD01C Protocol ImplementationIf no error occurs related to the Modbus function requested in a properly received Modbus ADU, the data field of a r
29 P94MOD01CReference6 Reference6.1 PID List with Modbus ValuesThis is a condensed PID List to show the corresponding Modbus 4X Registers for PIDs 1-
3 P94MOD01CContents1 Safety Information ...
30P94MOD01C ReferenceNOTE:In true Modbus, 3X and 4X Registers are numbered starting at 1. This is known as ‘one based’ addressing. However, when trans
31 P94MOD01CReferenceIndexNameTypeFormatEPMAccessDescription Range Unit RAMRegisters32bit Integer Access 4X Register #RAMRegister32bitFloat Access 4X
32P94MOD01C ReferenceIndexNameTypeFormatEPMAccessDescription Range Unit RAMRegisters32bit Integer Access 4X Register #RAMRegister32bitFloat Access 4X
33 P94MOD01CReferenceIndexNameTypeFormatEPMAccessDescription Range Unit RAMRegisters32bit Integer Access 4X Register #RAMRegister32bitFloat Access 4X
34P94MOD01C ReferenceIndexNameTypeFormatEPMAccessDescription Range Unit RAMRegisters32bit Integer Access 4X Register #RAMRegister32bitFloat Access 4X
35 P94MOD01CReferenceIndexNameTypeFormatEPMAccessDescription Range Unit RAMRegisters32bit Integer Access 4X Register #RAMRegister32bitFloat Access 4X
36P94MOD01C ReferenceIndexNameTypeFormatEPMAccessDescription Range Unit RAMRegisters32bit Integer Access 4X Register #RAMRegister32bitFloat Access 4X
37 P94MOD01CReferenceIndexNameTypeFormatEPMAccessDescription Range Unit RAMRegisters32bit Integer Access 4X Register #RAMRegister32bitFloat Access 4X
Lenze AC Tech Corporation630DouglasStreet•Uxbridge,MA01569•USASales:8002179100•Service:508278-9100www.lenze-actech.comP94MOD01D
4P94MOD01C Contents4.5 Controlling the Drive ... 22
5 P94MOD01CSafety Information1 Safety Information1.1 Warnings, Cautions & NotesGeneralSome parts of Lenze controllers (frequency inverters, serv
6P94MOD01C Safety InformationThe documentation contains information about installation in compliance with EMC (shielding, grounding, filters and cables
7 P94MOD01CIntroduction2 IntroductionThe following information is provided to explain how the PositionServo drive operates on a Modbus network; it is
8P94MOD01C Introduction2.3 Ethernet Port• Supported baudrates: 100Mbps and 10Mbps• Supports two simultaneous Modbus TCP/IP connections on port 502•
9 P94MOD01CInstallation3 InstallationSection 3.1 is only applicable to Modbus RTU communication with the EIA-485 (RS485) option module, E94ZARS41. Mod