Lenze E94P PositionServo Modbus User Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
18P94MOD01C
Commissioning
4.3.3 Modbus RTU Slave Node Settings
If using the EIA-485 (RS485) module, open MotionView and click on the [Communication] folder. Then select the
[RS485] folder to set/change the RS485 parameters: Configuration, Baud Rate, Parity, Stop Bits and Address.
Figure 14: RS-485 Folder
Configuration: ‘Modbus slave’ = the modbus slave protocol is enabled on the RS485 port.
UPPP = the RS485 uses UPPP (Point-to-Point Protocol).
Baud Rate: 115200bps, 57600bps, 38400bps, 19200bps, 9600bps
Parity: Even, Odd, None
Stop Bits: 2, 1.5, 1
Address: 1-247
Each slave device in the Modbus network must have its own unique network address. The ‘Addr’ submenu on
the drive display and the front panel buttons can be used to set the Modbus network address.
The RS485 default configuration is: UPPP, 19200bps, No Parity, 2 Stop Bits and Address = 1.
TIP - Avoid using address 1. Most Modbus devices ship with a default address of 1. As duplicate addressing
on a Modbus network is not allowed, this can lead to conflicts when replacing and commissioning nodes. To
avoid this it is recommended that you do not set the slave address to 1.
Modbus RTU Folder - Modbus Reply Delay
Modbus Reply Delay is the delay introduced after receiving a Modbus request and before sending a reply. Note
that this delay will always be >= 3.5 characters as required by the Modbus specification. Some Modbus master
devices are slower to respond than others and an increase of the ‘Modbus reply delay’ value may be required
to successfully work with these devices.
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 37 38

Comments to this Manuals

No comments