Lenze E94P PositionServo Modbus User Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
12P94MOD01C
Installation
• Maximum cable length for UTP/STP CAT5e cable is typically 100m. For other categories consult the cable
data sheet.
• Use fiber optic segments to:
• Extend networks beyond normal cable limitations.
• Overcome different ground potential problems.
• Overcome very high electromagnetic interference.
• Spurs or T connections are not permitted on an Ethernet cable. To create additional connections an Ethernet
switch must be used.
• The use of wireless networking products for industrial applications is becoming more acceptable, but
extreme care must be taken during the design phase and consultation with an industrial wireless provider
is strongly recommended.
3.3.4 Connections and Shielding: EIA-485
To ensure good system noise immunity all network cables should be correctly grounded:
• Minimum recommendation of grounding is that the network cable is grounded once in every cubical.
• Ideally the network cable should be grounded on or as near to each drive as possible.
• For wiring of cable to the connector plug the unscreened cable cores should be kept as short as possible;
recommended maximum of 20mm.
20
mm
max
C
onnect to
cubical panel/
ear
th (PE) as
close to driv
e
as possible
Figure 4: EIA-485 Connection
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 37 38

Comments to this Manuals

No comments