
Commissioning
Configuring the electrical shaft ("E−Shaft")
Electrical shaft via MotionBus (CAN) with PLC as electrical shaft master
6
221
EDBCSXP064 EN 8.0
Commissioning steps for a mimimum configuration
The codes can be found in the GDC in the "Positioning/E−shaft" menu item.
Setting Brief description
Preconditions l Wiring of the MotionBus (CAN) X4 with the master control (PLC) which acts as
electrical shaft master.
l Connection of a PC via the "Global Drive Control" (GDC) operating program to
the system bus (CAN) X14 for parameterisation.
l Information on selection and configuration of the control interface to control
the drive system can be found on 226.
Settings for the master (PLC)
1. Configure master control
as electrical shaft master.
l Set CAN node address of the CAN node.
l Set the same CAN baud rate for all nodes.
l Tx−COB−IDs; identifiers of the process data telegrams to the slaves
– The master transmits the process data to the slave drives via the process
data channel 1 (PDO1).
– The identifiers to be set of the individual output telegrams to the slaves
result from the CANopen convention:
Identifier = basic value + node address of the slave
– The slaves therefore only require few settings differing from the standard
settings for process data communication.
l Rx−COB IDs, identifiers of the process data telegrams from the slaves
– The telegrams sent back from the slaves via PDO1 are received by the
master.
– The identifiers of the individual telegrams in standard setting of the slaves
also correspond to the CANopen convention and are calculated as follows:
Identifier = basic value + node address of the slave
l Cyclically send a CAN sync telegram ( 420) with the identifier = 0x80.
l Master setpoint cycle; Interval in which the process data and the CAN sync
telegram are transmitted by the master
– The setpoint cycle is to amount to 2, 4 or 6 ms.
Note: The set interval time for the setpoint cycle must be complied exactly
with regard to a long−term medium.
A jitter of single CAN sync telegrams of up to one telegram runtime is
non−critical if the long−term medium is complied with. In case of CAN, delays
may occur due to telegrams being in transmission since running telegrams
cannot be interrupted.
l If required, provide for monitoring of the response telegrams from the slaves.
l Generation of the master value/master angle to be transmitted to the slaves
– Telegram structure see 158 and 161.
– The master angle is transmitted in bytes 5 ... 8 (PosDirect).
– Information on selection and configuration of the control interface to
control the drive system can be found on 226.
Settings for the slave drive
2. Carry out CAN settings. l C0350 = x; set the CAN node address of the CAN node.
l C0351 = 500 kbps; set the same CAN baud rate for all nodes.
3. Configure process data
channel 1 (PDO1) as
input channel.
l C4010 = 0; select control interface "CAN1 (PDO1, sync−controlled)".
l C0353/1 = 0; set the ID creation mode for CAN1_IN/OUT to "Identifier = base
value + node address C0350".
– C0355/1: Display of the identifier CAN1_IN of the slave
– C0355/2: Display of the identifier CAN1_OUT of the slave
Comments to this Manuals