Safety instructions
Residual hazards
1
EDKLM3−XXX−002 DE/EN/FR 1.0 23
l
H1sic_EN−Hi_festinst
Residual hazards
{ Danger!
Dangerous voltage
All power connections carry dangerous voltages both if the motor is at
standstill and after up to 3 minutes after mains switch off.
Possible consequences:
ƒ Death or severe injuries after touching the power connections.
Protective measures:
ƒ Wait for at least 3 minutes before working on the power connections.
ƒ Check whether all power connections are de−energised.
{ Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when the device is touched in the event of a fault.
Protective measures:
ƒ Implement the actions required in the EN 61800−5−1. Especially:
Fixed installation
PE connection must conform to standards (PE conductor diameter
³ 10 mm
2
or PE conductor must be connected twice)