Lenze DDS System bus CAN for PLC User Manual Page 142

  • Download
  • Add to my manuals
  • Print
  • Page
    / 178
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 141
9.4 CANaux_Management (node number: 111)
System bus (CAN) for Lenze PLC devices
CAN−AUX system blocks
9−6
L
PLC−Systembus EN 2.0
9.4.5 Status messages
The CANaux_Management SB provides different status messages which can be processed in the
PLC program:
Identifier Information
CANaux_bCe1CommErrCanIn1_b TRUE CANaux1_IN communication error
CANaux_bCe2CommErrCanIn1_b TRUE CANaux2_IN communication error
CANaux_bCe3CommErrCanIn1_b TRUE CANaux3_IN communication error
CANaux_bCe4BusOffState_b TRUE CAN−AUX−bus "off state" recognised
CANaux_byNodeAddress 1...63 CAN−AUX node address (^ 3−3)
CANaux_byState
Operating status of the system bus
1 Operational
2 Pre−operational
3 Warning
4 Bus−off