8.2 Extendability/networking
Drive PLC
Appendix
8−2
L
DrivePLC DE 6.0
8.2 Extendability/networking
U
V
T
S
z
Z
y
Y
SH PRG
p
PaR2 PaRa
0051
00
125 rpm0
MCTRL-N-ACT
GLOBAL DRIVE
d
cb
B
A
59 39
71
72
88
89
LECOM A/B
l
Automation interface (AIF)
for keypad and the following AIF modules:
2102 LECOM−A/B/LI
2103 FP interface (RS−232C)
2111 INTERBUS
2112 INTERBUS−Loop
2133 PROFIBUS−DP
2174 CAN addressing module
2175 DeviceNet / CANopen
Others in preparation
Plug−in station for extension boards
Function interface (FIF)
for FIF modules
Integrated system bus interface
(Terminal X5 at the bottom of the Drive PLC)
Extension boards
Inputs/outputs Number Description
Extension Board 1
Inputs digital 6 Free inputs 24 V DC / 8 mA each input
Outputs digital 6 Free outputs 24 V DC / max. 1 A each output
Extension Board 2
Inputs digital 14 Free inputs 24 V DC / 8 mA each input
Outputs digital 8 Free outputs 24 V DC / max. 1 A each output
extension board 3
Inputs
digital 6 Free inputs 24 V DC / 8 mA each input
analog 2 Free inputs (10 bit + sign) 10 V
1 Encoder input Frequency range:
HTL 0 ... 200kHz, TTL 0 ... 500kHz
(TTL/HTL level)
Outputs digital 6 Free outputs 24 V DC / max. 1 A each output
Modules for function interfaces (FIF)
Inputs/outputs Number Description
Standard I/O FIF module
Inputs
digital 5 Free inputs 24 V DC / 8 mA each input
analog 1 Free input (10 bit + sign) 10 V
Outputs
digital 1 Free output 24 V DC / max. 1 A
analog 1 Free output (10 bit + sign) 10 V / max. 2 mA
CAN−I/O FIF module
Inputs
digital 1 Free input 24 V DC / 8 mA
3 System bus (CAN), free inputs
Outputs System bus (CAN)