Parameterisation 8200 vector/8200 motec
Transmit parameter sets
7
EDK9371BC DE/EN/FR 3.1
79
H1 Parametrierung 8200−9371BC_6L
Transmit parameter sets
The keypad enables you to copy parameter settings from one standard device to another.
Use "Param managm" in menu 7 for this purpose:
Copy parameter sets from the standard device to the keypad
Step
Key sequence Action
1. Connect the keypad to
standard device 1
2. Inhibit the controller
#
The drive coasts
3. Select the "Load/Store"
submenu 7.1 in the "Param
managm" menu 7
!
Change to the "Load/Store" submenu
using the arrow keys
4. Change to the code level
"Param managm" is displayed in C0002
5. Change to the parameter level
"0" and "READY" are displayed
6.
Select the correct copy function The settings stored in the keypad are
overwritten.
l Copy all available parameter sets (PAR1 ... PAR4, FPAR1 if applicable) into the keypad:
Standard device with
function module
Application I/O,
INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen
Copy PAR1 ... PAR4 and FPAR1:
ð Set "80" "F1&PAR1−4−>Key"
Standard device with all
other function modules
Copy PAR1 ... PAR4:
ð Set "20" "PAR1−4−>Keypad"
l Only copy the module−specific parameter set FPAR1 to the keypad:
Only possible for
standard devices with
function module
INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen:
Copy FPAR1:
ð Set "50" "FPAR1−>Keypad"