Lenze E82ZAFSC001 User Manual Page 33

  • Download
  • Add to my manuals
  • Print
  • Page
    / 65
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 32
Technical data
Connection data
4
EDK82ZAFSC DE/EN/FR 5.0
33
H1_Daten−Einsatzbed_Klima_FIF
4 Technical data
Connection data
X3/ Values
62 Resolution: 10 bit
Linearity distortion: ±0.5 %
Temperature distortion: 0.3 % (0  +60°C)
Carrying capacity I
max
= 2 mA
8
Resolution: 10 bit
Linearity distortion: ±0.5 %
Temperature distortion: 0.3 % (0  +60 °C)
Input resistance
l R
Input
> 50 kW (with voltage signal)
l R
Input
= 250 W (with current signal)
9 Carrying capacity I
max
= 10 mA
7 isolated from terminal X3/39 (GND2)
20
Load capacity: S I
max
= 40 mA
28
Input resistance: 3.3 kW
1 = HIGH (+12  +30 V), PLC level, HTL
0 = LOW (0  +3 V), PLC level, HTL
E1
1)
E2
1)
E3
E4
39 isolated from terminal X3/7 (GND1)
A1 Load capacity:
I
max
= 10 mA, with internal supply
I
max
= 50 mA, with external supply
1)
Frequency input alternatively 0  10 kHz single−track or 0 ... 1 kHz two−track, config. via C0425
Operating conditions
Ambient conditions
Climate
Storage IEC/EN 60721−3−1 1K3 (−25 to +60 °C)
Transport IEC/EN 60721−3−2 2K3 (−25 to +70 °C)
Operation Corresponding to the data of the Lenze basic device used (see
documentation of the basic device).
Pollution EN 61800−5−1 Degree of pollution 2
Page view 32