Lenze EZN3x0015H230 User Manual Page 32

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 31
Technical data
General data and operating conditions
2
l
32
EDKZNXXXX−001 DE/EN/FR 3.0
2 Technical data
2.1 General data and operating conditions
Mains data
Mains types
With grounded neutral (TT/TN systems) Operation permitted without restrictions
Other mains types Observe instructions for special measures in the
documentation for the basic device!
Protection
Degree of protection EN 60529 IP 20 Not in the wire range of
the terminals
Insulation resistance EN 61800−5−1 Overvoltage category III
> 2000 m: Overvoltage category II
Leakage current EN 61800−5−1 > 3.5 mA Observe regulations and
safety instructions!
Ambient conditions
Temperature
Storage
−25 ... +60 °C
Transport −25 ... +70 °C
Operation −10 ... +55 °C
Current derating from +40 to +55 °C: 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating by 5 %/1000 m
Pollution EN 61800−5−1 Pollution degree 2
Vibration resistance EN 50178; IEC
61800−5−1;
Germanischer Lloyd,
general conditions
Acceleration−resistant up to 0.7 g
Mounting conditions
Mounting location In the control cabinet
Mounting position Between mounting plate and standard device (standard) or to the left of the
standard device (for controllers in push−through technique or in cold−plate
technique)
Mounting position Vertical, mains connection on top
Free spaces
at the top > 150 mm
at the bottom > 100 mm
to the sides > 100 mm