Troubleshooting and fault elimination
8200SHB0199
8-3
Display RemedyCauseFault
OC2 Earth fault
Grounded motor phase Check motor; check cable
Excessive capacitive charging current of
the motor cable
Use motor cable which is shorter or has a lower
capacitance
OC3 Overload inverter during
acceleration or short circuit
Accelerationtime tooshort (C012) Increase acceleration time
Check drive selection
Defective motor cable Check wiring
Interturn fault in the motor Check motor
OC4 Overload controller during
deceleration
Deceleration time tooshort (C013) Increase decelerationtime
Check the selection of the brake resistor or
connect the brake chopper
OC5 Ixtoverload
Frequent and too long acceleration
processes with overcurrent
Check drive selection
Permanent overload with
I
motor
>1.05xI
rx
OC6 Overload motor
Motoris thermallyoverloaded, for
instance, because of
impermissible continuous current Check drive selection
frequent or too long acceleration
processes
Check the setting under C120
OH Heat sink temperature is
higher than the value set in
the controller
Ambient temperature
T
amb
>+40Cor+50C
Allow controller to cool and ensure ventilation
Check the ambient temperature inthe control
cabinet
Heat sink very dirty Cleanheatsink
Incorrect mounting position Change mounting position
OH3 PTC monitoring
Motortoohot because of excessive
currents or frequent and too long
accelerations
Check drive selection
PTC not connected Connect PTC or switch-off monitoring
(C0585 = 3)
OH4 Overtemperature unit Inside unit too hot Reduce controller load
Improve cooling
Check fan in the controller
OU Overvoltage
Mains voltage too high Check voltage supply
Feedback operation
Braking operation
Prolongdeceleration times
For operation with brake choppers:
- Check the selection and connection of the
brake resistor
- Increase the deceleration times
Earth leakage onthe motor side Check motor cable and motor for earth fault
(disconnect motor from inverter)
OUE Overvoltage Mains overvoltage longer than 5 s Check mains voltage
Pr Faultyparametertransfer
via the operating module
PAR1 and PAR2 a re defective
Pr1 FaultyPAR1 transfer via the
operatingmodule
PAR1 is defective
transfer or load the factorysetting before
Pr2 FaultyPAR2 transfer via the
operatingmodule
PAR2 is defective
rSt Faulty auto-TRIP reset More than8 faultmessages in
10 minutes
Depends on the fault message